Title of article :
An efficient method for calculation of electric field in three-core power cables
Author/Authors :
Delgado Leon، نويسنده , , M.Z.، نويسنده , , Murari، نويسنده , , C.A.F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
6
From page :
1179
To page :
1184
Abstract :
In this paper we applied the Superposition Principle with a new basic conductor voltage condition for the computed electric field in three-core cables and the results obtained have higher accuracy and lower computational time than the previous works. The maximum potential errors is not more than 0.050% and the maximum field deviat8ion angle is not more than 0.011". The electric field problem under arbitrary conductor voltage condition is reduced to a field computation for a new basic conductor voltage condition (O,l,-1) which reduces the computing time because it doesnʹt require the repetitive solution of the algorithm for different ut values. With this new configuration, it is possible to take advantages of a symmetrical conductor arrangement, reducing the number of charges necessary for the field calculation and the Superposition Principle is applied only two times.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399175
Link To Document :
بازگشت