500-kV XLPE-insulated cable with an insulation thickness
of 27 nim and its joint have been developed for long distance
transmission lines. First, in the basic research made irom 1989 to
1992, elicited were the perfortnance-detertnining factors of XLPE
cables and joints. Their respective insulation designs were inade in
terms of these factors. On the basis of these designs, full-sized
cables and joints were manufactured in the course of the development
research performed from 1Y92 to 1993. The next step was to
evaluate the initial clectrieal pcrforinance to estimate the suitability
of our designs. As the final step of our series of researchcs so far
carried out, a long-term loading cycle test was carried out by means
of a model line with joints as insValled and using the same lechniques
as employed in the actual commercial lines for full eight
months. We could thus verify the long-term reliabilily for coniinercia1
use.