Title of article :
Validation of phasor calculations in the macrodyne PMU for California-Oregon Transmission Project tests of March 1993
Author/Authors :
Hauer، نويسنده , , J.F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
Faults applied during March 1993
commissioning tests for the California-Oregon
Transmission Project produced 14 Hz transient
oscillations that were conspicuous in BPAʹs enhanced
transducers at Malin, and in PG&Eʹs Dynamic System
Monitor at Table Mountain. Prony analysis of high
speed fault data provided a detailed model for the
underlying network resonance signal, and a basis for
validating transient performance of a Macrodyne
Phasor Measurement Unit (PMU) at the test site. This
instrument, which is closely associated with EPRIʹs
FACTS project, provides useful insight into emerging
technology for high speed digital transducers. The
phasor calculations are found to be of very high
quality, but filtering enhancements are recommended
for broadband applications.
Keywords :
FACTS , feedbackcontrol , Prony analysis , Phasor measurements , network resonances.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY