Title of article :
Fault component reactance relay
Author/Authors :
Shengshi Zhu، نويسنده , , Yibao Xing، نويسنده , , Fenghai Sui، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
9
From page :
1292
To page :
1300
Abstract :
A new distance relay is developed in this paper.The relay is based on two operation criteria - - - - acurrent criterion and a voltage criterion. Eachuses the fault component as operating quantity, andthe relay reacts only on the reactance of the trans-mission line. So, it is a fault component reactancerelay. During external fault, two criteria arecomplementary each other, i. e. at least one of themrill not be satisfied. So no maloperation will happen. During internal fault both criteria will be satisfied even if the fault resistance is high.
Keywords :
Distance relay , fault component , reactance relay
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399189
Link To Document :
بازگشت