Title of article :
Reduction of interference on substation low voltage wiring
Author/Authors :
Gavazza، نويسنده , , R.J.، نويسنده , , Wiggins، نويسنده , , C.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
13
From page :
1317
To page :
1329
Abstract :
This paper describes test results and mitigation methods of electromagnetic interference @MI) on control and low voltage circuits in substations caused by air disconnect switch operation. The tests are focused on a comparison between unshielded and shielded circuits from capacitively coupled voltage transformers (CCVT) and other equipment circuits in the vicinity. New test data are presented comparing unshielded and shielded cables and transient currents on all connections to the CCVT including the pedestal and ground strap. The paper gives a practical and understandable explanation of the causes of EM1 in substations and how shielded cable and parallel ground conductors reduce interference. Design guidelines are listed in the Conclusion.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399192
Link To Document :
بازگشت