• Title of article

    Calculation of single phase AC and monopolar DC hybrid corona effects

  • Author/Authors

    Zhao، نويسنده , , T.، نويسنده , , Sebo، نويسنده , , S.A.، نويسنده , , Kasten، نويسنده , , D.G.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    10
  • From page
    1454
  • To page
    1463
  • Abstract
    Operating a hybrid HVac and HVdc line is an option for increasing the efficiency of power transmission and overcoming the difficulties in obtaining a new right-of-way. This paper proposes a new calculation method for the study of hybrid line corona. The proposed method can be used to calculate dc corona losses and corona currents in dc or ac conductors for single phase ac and monopolar dc hybrid lines. Profiles of electric field strength and ion current density at ground level can be estimated. The effects of the presence of an energized ac conductor on dc conductor corona and dc voltage on ac conductor corona are included in the method. Full-scale and reduced-scale experiments were utilized to investigate the hybrid line corona effects. Verification of the proposed calculation method is given.
  • Keywords
    Hybrid lines , electric fieldstrength , corona current computation , ion current density , reduced-scale modeling. , Corona current
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399210