• Title of article

    Calculation of electric field and audible noise from transmission lines with non-parallel conductors

  • Author/Authors

    Yilu Liu، نويسنده , , Enea Zaffanella، نويسنده , , L.E.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    6
  • From page
    1492
  • To page
    1497
  • Abstract
    In order to investigate the feasibility of using new transmission line configurations with non-parallel conductors, for managing magnetic field in critical areas, techniques are needed to assess the effects of different three-dimensional line arrangements on other important design parameters. A new method for calculation of electric field and corona-generated audible noise from non-parallel conductors is described and implemented as a computer tool. This method uses linearly varying line charges to simulate charge distribution along the axial direction of the transmission line. New algorithms are developed for calculating electric field and audible noise due to non-uniform line charges and illustrated by examples of low magnetic field transmission line designs.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number