Title of article :
Accurate modelling of rod driven tower footing
Author/Authors :
Almeida، نويسنده , , M.E.، نويسنده , , Correia De Barros، نويسنده , , M.T.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
For evaluating the lightning performance of
transmission lines by computer simulation, the accurate
modelling of tower footing is very important. In particular, the
decrease of the earth resistance observed for high values of the
current flowing from the tower to earth has to be considered.
In this paper, different modelling approaches allowing to take
into accouut the non-linear behaviour of the tower footing are
overviewed, and a uew model to describe the soil ionization
process is presented. The proposed model corresponds to
considering the ionized soil region as an equifield shell. In
order to represent the ionization phenomena, the values of the
resistivity on the ionized region are decreased according to the
local current density, and the electric field is kept at a critical
value. Deionization of the soil is also taken into account.
Simulation results are presented, and compared to the
published results of experimental tests.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY