Title of article :
Identification and tracking of harmonic sources in a power system using a Kalman filter
Author/Authors :
Haili Ma، نويسنده , , Girgis، نويسنده , , A.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
7
From page :
1659
To page :
1665
Abstract :
In this paper, two problems have been addressed on harmonic sources identification: the optimal locations of a limited number of harmonic meters and the optimal dynamic estimates of harmonic source locations and their injections in unbalanced three-phase power systems. A Kalman filtering is used to attack these problems. System error covariance analysis by the Kalman filter associated with a harmonic injection estimate determines the optimal arrangement of limited harmonic meters. Based on the optimally-arranged harmonic metering locations, the Kalman filter then yields the optimal dynamic estimates of harmonic injections with a few noisy harmonic measurements. The method is dynamic and has the capability of identifying, analyzing and tracking each harmonic injection at all buses in unbalanced threephase power systems. Actual recorded harmonic measurements and simulated data in a power distribution system are provided to prove the efficiency of this approach.
Keywords :
Harmonic sources identification , Kalman filter , Optimal dynamic estimate , Optimal metering locations.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399237
Link To Document :
بازگشت