Title of article :
Verification of measured transmission system phase angles
Author/Authors :
Wilson، نويسنده , , R.E.، نويسنده , , Sterlina، نويسنده , , P.S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
5
From page :
1743
To page :
1747
Abstract :
Measurement of power system phase angle is being studied for use in protective relaying, critical control circuits, and other applications. This paper compares phase angles measured by a synchronized measuring unit during field testing with classical theory. Power system positive sequence voltage and current phasors were recorded during testing of a new 525 kV compensated transmission system. Steady-state phase angles (6) and magnitudes were measured relative to a satellitebased global time standard on synchronized measurement units at two substations. Phase angles were calculated using recorded supervisory system and sending-end values of total power flow. Field measurements of the phase angle across a transmission system differed from calculations by -0.09" on the average, contributing to verification of the new synchronized measurement technique.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399250