Verification of measured transmission system phase angles
Author/Authors :
Wilson، نويسنده , , R.E.، نويسنده , , Sterlina، نويسنده , , P.S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
Measurement of power system phase angle is being
studied for use in protective relaying, critical control circuits,
and other applications. This paper compares phase angles
measured by a synchronized measuring unit during field testing
with classical theory. Power system positive sequence voltage
and current phasors were recorded during testing of a new 525
kV compensated transmission system. Steady-state phase
angles (6) and magnitudes were measured relative to a satellitebased
global time standard on synchronized measurement units
at two substations. Phase angles were calculated using recorded
supervisory system and sending-end values of total power
flow. Field measurements of the phase angle across a transmission
system differed from calculations by -0.09" on the average,
contributing to verification of the new synchronized measurement
technique.