Title of article
A special-case surface voltage gradient formula [for substation design]
Author/Authors
Larsson، نويسنده , , A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
5
From page
1771
To page
1775
Abstract
In the electrical design of a high-voltage substation,
the designer needs a simple and reliable tool, preferably a
closed-form formula, when calculating the surface voltage gradient
of line segments within the substation since the surface
voltage gradient is the governing parameter of the corona performance.
This paper presents a derivation of a closed-form
formula for calculation of the maximum surface voltage gradient
of a special line configuration, namely a horizontal AC
three-phase Pine configuration with bundle conductors consisting
of three sub-conductors in a horizontal arrangement. The
formula has been verified against exact calculations and was
found to have an error less than 5% for all practical combinations
of the conductor radius, the sub-conductor spacing, the
phase distance, and the height above earth.