• Title of article

    EHV transformer bank unbalance: practical issues and solutions

  • Author/Authors

    Gutman، نويسنده , , R.، نويسنده , , Wagenaar، نويسنده , , L.B.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    6
  • From page
    1830
  • To page
    1835
  • Abstract
    An unconventional tap configuration has been implemented in AEP’s South Canton 7651345134.5 kV, 3-500 MVA transformer bank to counter the combined effects of impedance mismatch within the bank and natural unbalance of the extra-high-voltage (EHV) transmission system. These effects manifest themselves as unequal phase voltages and loadings and as elevated neutral and tertiary circulating currents in the bank, capable of reaching high magnitudes during heavy loading conditions. This paper describes the South Canton bank unbalance, the concerns it raised, and the actions taken by AEP to control its possible adverse effects on the integrity and operation of the South Canton Station facilities.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number