In HVDC transmission lines, a special
phenomenon, so called single unit flashover, is observed under
some special conditions. Only one or two insulator units repeat
flashovers, not resulting in an overall flashover along the string.
However, higher magnitudes of audible noise, radio and
television interferences, may give a serious problem.
Based on the investigation on k 500-kV full scale insulator
strings, higher occurrence probability of single unit flashovers
under cold-wet-switch-on conditions was clarified compared
with normal continuous operating voltage conditions.
Effectiveness of our newly proposed countermeasures to
prevent single unit flashovers was demonstrated by experiments
in laboratory and in field.