Title of article :
Voltage escalation and reignition behavior of vacuum generator circuit breakers during load shedding
Author/Authors :
Glinkowski، نويسنده , , M.T.، نويسنده , , Gutierrez، نويسنده , , M.R.، نويسنده , , Braun، نويسنده , , D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
This paper focuses on multiple reignitions and voltage
escalation that may occur during load shedding
when vacuum circuit-breakers are used as generator
circuit-breakers. The probability of multiple reignitions
and voltage escalation is proportional to the arc
angle and is very small. However, repeated reignitions
and voltage escalation may be observed in vacuum
switching devices after opening operations due to their
ability to interrupt high frequency currents. The transformer
side capacitance and the magnitude of the load
shedding play a significant role in developing repeated
reignitions and voltage escalation when vacuum circuit
breakers are used as generator circuit breakers. Of particular
concern is the case when a protective capacitor
is connected to the system side of the circuit breaker.
Although this capacitor reduces the magnitude of the
Dansient Recovery Voltage, it decreases the transient
frequencies and increases the reignition current that
flows through the vacuum circuit breaker after a voltage
breakdown. In all the cases under study, the reignition/
escalation problems are more severe with the
protective capacitor connected to the system for relative
low load shedding at short arc angles.
Keywords :
Modeling Generator Circuit Breakers , transientresponse , Escalation Voltages , Circuit Breaker Reignition , Circuit Breaker Restrike , Load shedding , Electromagnetic TransientProgram , Vacuum CircuitBreakers
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY