Title of article :
Voltage escalation and reignition behavior of vacuum generator circuit breakers during load shedding
Author/Authors :
Glinkowski، نويسنده , , M.T.، نويسنده , , Gutierrez، نويسنده , , M.R.، نويسنده , , Braun، نويسنده , , D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Pages :
8
From page :
219
To page :
226
Abstract :
This paper focuses on multiple reignitions and voltage escalation that may occur during load shedding when vacuum circuit-breakers are used as generator circuit-breakers. The probability of multiple reignitions and voltage escalation is proportional to the arc angle and is very small. However, repeated reignitions and voltage escalation may be observed in vacuum switching devices after opening operations due to their ability to interrupt high frequency currents. The transformer side capacitance and the magnitude of the load shedding play a significant role in developing repeated reignitions and voltage escalation when vacuum circuit breakers are used as generator circuit breakers. Of particular concern is the case when a protective capacitor is connected to the system side of the circuit breaker. Although this capacitor reduces the magnitude of the Dansient Recovery Voltage, it decreases the transient frequencies and increases the reignition current that flows through the vacuum circuit breaker after a voltage breakdown. In all the cases under study, the reignition/ escalation problems are more severe with the protective capacitor connected to the system for relative low load shedding at short arc angles.
Keywords :
Modeling Generator Circuit Breakers , transientresponse , Escalation Voltages , Circuit Breaker Reignition , Circuit Breaker Restrike , Load shedding , Electromagnetic TransientProgram , Vacuum CircuitBreakers
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1997
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399318
Link To Document :
بازگشت