Title of article
Performance of series-compensated line circuit breakers under delayed current-zero conditions
Author/Authors
Que Bui-Van، نويسنده , , Khodabakhchian، نويسنده , , B.، نويسنده , , Landry، نويسنده , , M.، نويسنده , , Mahseredjian، نويسنده , , J.، نويسنده , , Denise Y. Mainville، نويسنده , , J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
7
From page
227
To page
233
Abstract
Transient analysis studies of the
Hydro-Quebec 735- kV series-compensated network
with the ideal switch representation for line circuit
breakers exhibit the occurrence of abnormally delayed
current-zero crossings under some fault conditions.
The discovery of this phenomenon has triggered specific
studies to verify the performance of existing air- blast
circuit breakers and to draft the technical specifications
of future SF6 gas circuit breakers.
Keywords
series-compensation , Transient analysis , breaker arc model , delayed current-zero
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1997
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399319
Link To Document