Title of article :
Performance of series-compensated line circuit breakers under delayed current-zero conditions
Author/Authors :
Que Bui-Van، نويسنده , , Khodabakhchian، نويسنده , , B.، نويسنده , , Landry، نويسنده , , M.، نويسنده , , Mahseredjian، نويسنده , , J.، نويسنده , , Denise Y. Mainville، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Pages :
7
From page :
227
To page :
233
Abstract :
Transient analysis studies of the Hydro-Quebec 735- kV series-compensated network with the ideal switch representation for line circuit breakers exhibit the occurrence of abnormally delayed current-zero crossings under some fault conditions. The discovery of this phenomenon has triggered specific studies to verify the performance of existing air- blast circuit breakers and to draft the technical specifications of future SF6 gas circuit breakers.
Keywords :
series-compensation , Transient analysis , breaker arc model , delayed current-zero
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY