Title of article
An improved transformer top oil temperature model for use in an on-line monitoring and diagnostic system
Author/Authors
Lesieutre، نويسنده , , B.C.، نويسنده , , Hagman، نويسنده , , W.H.، نويسنده , , Kirtley، نويسنده , , J.L.، نويسنده , , Jr.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
8
From page
249
To page
256
Abstract
In this paper we examine dynamic models
of transformer top oil temperature for use in an on-line
monitoring and diagnostic system. Data taken from large
transformers in the field indicate that the IEEE model of
top oil temperature rise over ambient temperature does
not adequately account for daily variations in ambient
temperature. We propose a modification that acciirately
predicts top oil temperature and can be implemented in
an on-line system. This model is verified using data from
a large transformer in service.