Author/Authors :
Pilotto، نويسنده , , L.A.S.، نويسنده , , Ping، نويسنده , , W.W.، نويسنده , , Carvalho، نويسنده , , A.R.، نويسنده , , Wey، نويسنده , , A.، نويسنده , , Long، نويسنده , , W.F.، نويسنده , , Alvarado، نويسنده , , F.L.، نويسنده , , Edris، نويسنده , , A.، نويسنده ,
Abstract :
The paper presents an approach for identifiing the
most effective Flexible AC Transmission System (FACTS)
Controllers, locations, types and ratings that increase asset
utilization of power systems The approach is a combined
static/dynamic procedure based on the use of a continuation
power flow, an optimal power flow and an eigenvalue analysis
The application of this approach on a representative studied
transmission system has resulted in an increase of the maximum
stable loadability limit by 6 7 % The paper finally shows that the
proposed approach is helpful in coordinating the functionality of
FACTS Controllers to enhance power system dynamics
Keywords :
Voltage collapse , Electromechanical Stability , FACTS Controllers , HVDC Transmission