Automation of the ANSI C119.4-1991 connector test
Author/Authors
Hutchinson، نويسنده , , T.F. ، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
5
From page
560
To page
564
Abstract
Automation of the ANSI (319.4-1991 connector
test has been expensive. The ANSI test requires accelerated
aging using ac current. The resistance of each connector must
be measured periodically using dc current. These requirements
generate the need for two power sources switched in and out by
a computer-controlled relay. This relay must have contact
current carrying capabilities equal to that of the cable on test.
For large conductor sizes this expense becomes formidable.
A method of making accurate ohm measurements of the
connectors without connecting or disconnecting the conductor is
given in this paper. Automation of the test can be established
for a minimal investment with the information given.
Automation will allow more information to be gathered, which
will lead to the connector aging process being better understood
and controlled.