Title of article
Application of current limiting fuses in distribution systems for improved power quality and protection
Author/Authors
Kojovic، نويسنده , , L. Hassler، نويسنده , , S. ، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
10
From page
791
To page
800
Abstract
This paper presents a comparative analysis
of the effects of distribution system expulsion and
current limiting fuse operations on power quality. To
perform this analysis, digital fuse models were
developed for use with the EMTPIATP program.
Expulsion fuses interrupt current at current zeros and
are easily modeled. Current limiting fuses (CLFs)
interrupt current by forcing a current zero and therefore,
require a special modeling technique. CLFs were
modeled by representing them as non-linear
resistances. The non-linear resistances were calculated
using laboratory test results of actual CLF operations.
This technique is very convenient for simulating CLF
operations and analyzing their interaction with the
distribution system. This paper shows that CLFs
improve power quality by supporting system voltage
during faults and reducing voltage dip duration.
Additionally, CLFs reduce the fault let-through I2t.
Keywords
Fuse , Current Limiting Fuse , modeling , EMTP , ATP , distribution systems , power quality
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1997
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399391
Link To Document