Title of article :
Power differential method for discrimination between fault and magnetizing inrush current in transformers
Author/Authors :
Yabe، نويسنده , , K.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Pages :
10
From page :
1109
To page :
1118
Abstract :
To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for blocking differential relay in power transformers. However, the second harmonic component in fault current is increased by the introduction of underground 500kV lines. This paper describes a new method to discriminate internal fault from inrush current by the sum of active power flowing into transformers from each terminal. The average power is almost zero for energizing, but an inlernal fault consumes large power. To check the performance of this method, actual inrush current and voltage waveforms of 500/154kV transformer are accurately measured by digital equipment. The usefulness is confirmed by applying the method to the measured inrush and simulated fault data.
Keywords :
Transformer protection , Active powerrelays , Magnetizing inrush , Microprocessor-basedrelays , Protection relays
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1997
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399434