Title of article
Capacitive divider substation
Author/Authors
Bolduc، نويسنده , , L.، نويسنده , , Bouchard، نويسنده , , B.، نويسنده , , Beaulieu، نويسنده , , G.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
8
From page
1202
To page
1209
Abstract
The development of a passive damper-filter has
made it possible to achieve a stable capacitive-coupling
substation (SCC). This paper presents the underlying theory and
analyzes the impact of the SCC on a power network system. The
related nuisance phenomena (overvoltage, ferroresonance) are
described together with the solutions applied. Test results are
presented as proof that the nuisance phenomena have been
satisfactorily eliminated: overvoltage is adequately limited at the
worst node by protecting the equipment and ferroresonance
never lasts more than two cycles. Lastly, the paper describes
Hydro-Qukbecʹs first such capacitive-coupling substation
installed at RivMre Ste-Anne (Qukbec).
Keywords
Capacitive Substation , Capacitive Divider , Rural Electrification.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1997
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399445
Link To Document