Title of article :
Survey of harmonic voltage and current at distribution substation in Northern Taiwan
Author/Authors :
Chung-Hsing Hu، نويسنده , , Chi-Jui Wu، نويسنده , , Shih-Shong Yen، نويسنده , , Yun-Wu Chen، نويسنده , , Bor-An Wu، نويسنده , , Jan-San Hwang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
This paper presents a survey of voltage and
current harmonic distortion levels at 40 power transformers
and 10 capacitor units in Northern Taiwan. Through one year
measurement, about 12,000 sets of harmonic voltage and
current data are recorded and analyzed. The types and levels
of liarmonics are showed in each power transformer which
supplies different residential, commercial, and industrial
customers with various loads. At the same time, a suggestion
is given to the representative value of background level of
harmonic voltages with 95% cumulative probability which is
adopted by Taipower. At last, effects of harmonics on
capacitors and power transformers are discussed.
Keywords :
Harmonics , Survey , distribution substation , electric power quality.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY