Title of article :
Audible noise performance of 6-rail conductors on a 765-kV double circuit test line
Author/Authors :
Dong Il Lee، نويسنده , , Jeong Boo Kim، نويسنده , , Koo Yong Shin، نويسنده , , Kwang Ho Yang، نويسنده , , Hee Sung Ahan، نويسنده , , Ja Yoon Koo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
To satisfy an annual rate load
growth of approximately 10% per year, Korea Electric
Power Corporation (KEPCO) has been studying the use of
double circuit 765-kV transmission lines. Since this would
be the first application in the world for such lines, a
765-kV test line was built near the Yellow Sea to gain
experience with this higher voltage. A primary corona
phenomena that is important for conductor selection is
audible noise (AN) due to corona. This paper presents the
results of long-term measurements of AN from the 765-kV
double circuit test line using a bundle of 6-483.8 mot
conductors at Korea Electric Power Research Instituteʹs
(KEPItI) 765-kV test station. The analysis of the data
shows that the 6-Rail conductor bundle satisfies the AN
criterion of 50 dB(A) under rainy weather conditions.
Keywords :
Test Line , corona , Environmental impacts , audible noise
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY