• Title of article

    A useful methodology for analyzing distance relays performance during simple and inter-circuit faults in multi-circuit lines

  • Author/Authors

    Agrasar، Zulma R?golo de نويسنده , , M.، نويسنده , , Uriondo، نويسنده , , F.، نويسنده , , Hernandez، نويسنده , , J.R.، نويسنده , , Alvarez، نويسنده , , R.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    7
  • From page
    1465
  • To page
    1471
  • Abstract
    A methodology for evaluating and visualising the response of distance units most commonly used is presented. A general case, with different topologies, of a double circuit line is considered and different types of inter-circuit faults are treated. Single line and simple faults are simplified cases of the general one. Faults are treated by means of the adequate connection between the sequence networks, where different types of faults are represented by a resistances star associated to both lines and ground. Different combinations of these resistances result in different types of faults. Fault conditions are introduced to sequence networks of the rest of the system through phase current controlled current sources, and the resulting sequence voltages at the fault point are applied to fault resistances through sequence voltage controlled voltage sources. To calculate faults the mesh analysis method has been modified to take into account the dependencies fixed by the controlled sources. Real previous state of the Power System (load flow, sequence source impedances at both ends and sequence impedance between ends) is taken into account. A useful and reliable way of representation is presented to obtain the expected response of different types of distance units in multi-circuit lines in presence of inter-circuit simultaneous faults.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399478