Author/Authors :
Saha، نويسنده , , T.K.، نويسنده , , Darveniza، نويسنده , , M.، نويسنده , , Hill، نويسنده , , D.J.T.، نويسنده , , Le، نويسنده , , T.T.، نويسنده ,
Abstract :
This paper describes the application of two
relatively new diagnostic techniques for the determination
of insulation condition in aged transformers. The
techniques are (a) measurements of interfacial polarization
spectra by a DC method and (b) measurements of
molecular weight and its distribution by gel permeation
chromatography. Several other electrical properties of
the cellulose polymer were also investigated. Samples
were obtained from a retired power transformer and
they were analysed by the developed techniques. Six
distribution transformers were also tested with the interfacial
polarization spectra measurement technique,
and the molecular weight of paper/pressboard samples
from these transformers were also measured by the gel
permeation chromatography. The variation of the results
through different locations in a power transformer
is discussed in this paper. The possible correlation between
different measured properties was investigated
and discussed in this paper.