Title of article :
A procedure for derating a substation transformer in the presence of widespread electric vehicle battery charging
Author/Authors :
Staats، نويسنده , , P.T.، نويسنده , , Grady، نويسنده , , W.M.، نويسنده , , Arapostathis، نويسنده , , A.، نويسنده , , Thallam، نويسنده , , R.S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
This paper studies the effect of electric vehcle
(EV) battery charging on a substation transformer that
supplies commercial, residential, industrial, and EV load on a
peak summer day. The analysis begins by modeling non-EV
load with typical utility load shapes. EV load is modeled
using the results from an analytical solution technique that
prehcts the net power and harmonic currents generated by a
group of EV battery chargers. We evaluate the amount of
transformer derating by maintaining constant daily
transformer loss-of-life, with and without EV chargmg. This
analysis shows that the time of day and the length of time
during which the EVs begin charging are critical in
determining the amount of transformer derating required.
Our results show that with proper control, EV charging may
have very little effect on power system components at the
substation level.
Keywords :
Electric Vehicles , Transformer Derating , Battery Chargers , Harmonics.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY