Energy absorption of surge arresters on power distribution lines due to direct lightning strokes-effects of an overhead ground wire and installation position of surge arresters
Author/Authors
Nakada، نويسنده , , K.، نويسنده , , Yokota، نويسنده , , T.، نويسنده , , Yokoyama، نويسنده , , S.، نويسنده , , Asakawa، نويسنده , , A.، نويسنده , , Nakamura، نويسنده , , M.، نويسنده , , Taniguchi، نويسنده , , H.، نويسنده , , Hashimoto، نويسنده , , A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1997
Pages
7
From page
1779
To page
1785
Abstract
We describe the characteristics of energy
absorption of surge arresters on power distribution lines due to
direct lightning strokes. Using the EMTP, the effect of an
overhead ground wire and the influence of the installation
position of a surge arrester on the energy absorption are
investigated quantitatively. The analysis shows that: (1) an
overhead ground wire is more effective to prevent damage to
surge arresters than increasing the withstand capabilities of
surge arresters by a factor of two, (2) the energy absorption
without an overhead ground wire is about 3-5 times larger than
that with one, and (3) in the case of direct lightning strokes to an
overhead ground wire, the energy absorption of surge arresters
installed at the termination of a line is approximately 2.3 times
larger at maximum than that of arresters installed in the midst ofa
line.
Keywords
lightning , SurgeArrester , Overhead Ground Wire. , Power Distribution Line