Author/Authors :
Hvidsten، نويسنده , , S.، نويسنده , , Ildstad، نويسنده , , E.، نويسنده , , Holmgren، نويسنده , , B.، نويسنده , , Werelius، نويسنده , , P.، نويسنده ,
Abstract :
This paper describes experiments performed on laboratory
aged 12kV and service aged 24 kV XLPE cable samples.
Results from measurements of residual ac breakdown
strength, degree of water treeing and dissipation factors are
presented.
The dissipation factor at low frequencies was determined by
both time and frequency domain measurements. Relation
between these methods are discussed, and it is shown that both
can be used for assessing the average ageing state of the cable.
The results show that water treeing causes reduced residual ac
breakdown strength, high and non-linearly increasing low-frequency
dielectric loss.