Harmonic impedance measurement using three-phase transients
Author/Authors
Nagpal، نويسنده , , M.، نويسنده , , Xu، نويسنده , , W.، نويسنده , , Sawada، نويسنده , , J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
6
From page
272
To page
277
Abstract
In this paper, a technique is presented for measuring the
harmonic impedances of an unbalanced three-phase distribution feeder.
The technique uses transients in bus voltages and feeder currents
generated by several close-trip operations of the shunt capacitor bank. The
work is based on the assumption that the impedance of feeder does not
change over time during which the switching operations are performed.
Mathematical development of the technique is verified with the laboratory
and the field tests. The technique provided good measurements of the
harmonic impedances up to 1.5 kHz for the given capacitor sizes.
Statistid indices were developed to assess the accuracy of the estimated
impedance values.
Keywords
Feeder load model , harmonic impedance , Transient signalmeasurements.