• Title of article

    Retrofitting-new high voltage XLPE cables substituting paper-insulated power cables in steel pipes

  • Author/Authors

    Bannach، نويسنده , , D.، نويسنده , , Kirchner، نويسنده , , M.، نويسنده , , Neubert، نويسنده , , R.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    5
  • From page
    287
  • To page
    291
  • Abstract
    Many utilities still have paper-insulated pipe type cables in service. In the near future they may have to replace some of these systems due to local increases in electric power demand or aged cable insulation. In many cases the steel pipes are well protected against corrosion and thus suitable for further use. For Retrofitting in such installations, XIAPE-insulated cables offer several advantages. Felten & Guilleaunie Energietechnik AG has developed a new three-core XLPE-insulated 64/110 kV cable with reduced insulation thickness (10 mm), that (can be pulled into a pipe. In co-operation with VEW ENERGIE AG, the cable performance is being investigated in a field test, that started in October 1996. This long-term loading cycle test will last for three years. The test voltage, applied between conductor and earth, amounts to 127 kV. The temperature is measured with the help of an optical-fiber measurement system. This device is computer controlled and works as a remote monitoring system.
  • Keywords
    power cables , pipe cables , optical-fiber measurements , cable ratings , power cable installation , Trenchless technology , Retrofitting , cross linked polyethyleneinsulation , temperature measurement , paper insulation
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number