Title of article
Retrofitting-new high voltage XLPE cables substituting paper-insulated power cables in steel pipes
Author/Authors
Bannach، نويسنده , , D.، نويسنده , , Kirchner، نويسنده , , M.، نويسنده , , Neubert، نويسنده , , R.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1998
Pages
5
From page
287
To page
291
Abstract
Many utilities still have paper-insulated pipe type cables
in service. In the near future they may have to replace some of these
systems due to local increases in electric power demand or aged
cable insulation. In many cases the steel pipes are well protected
against corrosion and thus suitable for further use. For Retrofitting
in such installations, XIAPE-insulated cables offer several advantages.
Felten & Guilleaunie Energietechnik AG has developed a new
three-core XLPE-insulated 64/110 kV cable with reduced insulation
thickness (10 mm), that (can be pulled into a pipe. In co-operation
with VEW ENERGIE AG, the cable performance is being investigated
in a field test, that started in October 1996. This long-term
loading cycle test will last for three years. The test voltage, applied
between conductor and earth, amounts to 127 kV. The temperature
is measured with the help of an optical-fiber measurement system.
This device is computer controlled and works as a remote monitoring
system.
Keywords
power cables , pipe cables , optical-fiber measurements , cable ratings , power cable installation , Trenchless technology , Retrofitting , cross linked polyethyleneinsulation , temperature measurement , paper insulation