• Title of article

    Mechanism for impulse conversion of water trees to electrical trees in XLPE

  • Author/Authors

    Boggs، نويسنده , , S.، نويسنده , , Densley، نويسنده , , J.، نويسنده , , Kuang، نويسنده , , J.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    6
  • From page
    310
  • To page
    315
  • Abstract
    A lightning impulse causes substantial capacitive current in a water tree channel which, as a result of its small cross section, has relatively low conductance. Transient, nonlinear finite element computations with coupled thermal and electric fields for the geometry of a 15 kV XLPE dielectric cable indicate that an 80 kV lightning impulse can cause the water within a water tree channel to boil over a range of four orders of magnitude in water conductivity, from IO2 S/m to IO2 S/m. Boiling of the water in a water tree channel reduces substantially the yield stress of the XLPE, raises the pressure within the water tree channel, and is likely to leave a cavity which can support partial discharge resulting in electrical tree initiation.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1998
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399550