Abstract :
We measured the temporal change of partial
discharge (PD) characteristics leading to breakdown in SF,
gas for ac voltage application. At the final stage close to the
breakdown, positive PD pulses with relatively high magnitude
began to take place in the phase region near the applied voltage
peak. This event was interpreted in terms of the change of PD
type in SF6 gas from streamer to leader. Optical observation
also revealed that PD type transition occurred. With the results
considered, the mechanisms of PD were discussed.
Moreover, we discussed the possibility of breakdown
prediction in GIs. An attempt was made to find a breakdown
prediction parameter which characterized the change of PD
type: the ratio RL of maximum charge to the average charge
of PD pulses appearing in the phase region near the peak in
positive half cycle. It was found that R, allowed to predict the
time to breakdown successfully within the error of 4 - 20 %.