Title of article :
Relation of insulation resistance and deteriorated ratio of reference voltage of oil-immersed surge arrester elements enclosed in pole transformers
Author/Authors :
Uchida، نويسنده , , S.، نويسنده , , Mochizuki، نويسنده , , K.، نويسنده , , Araki، نويسنده , , K.، نويسنده , , Kaku، نويسنده , , I.، نويسنده , , Sakuraba، نويسنده , , Y.، نويسنده , , Takeshina، نويسنده , , T.، نويسنده , , Shirakawa، نويسنده , , S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
6
From page :
453
To page :
458
Abstract :
About. t,en years have passed since oil immersed surge arrester elements enclosed in 6.GkV pole transformers been used. At, present, technical developments are being demanded t,o judge t,he soundness of these oil immersed surge arrester element,s by a simple method and easily judge whet.her t,hese elements can he usecl or not. on site The authors empirically investigat,ed correlation bet,ween t.he insulation resist,ance and the rleteriorat,ecl ratio of t,he reference volt,age of t.hese oil-immersed surge arrester elements. It was found that t,he det,eriorat,ion of the oil-immersed surge arrester elements can be det,ectecl by measuring t,he insulation resistance by a megger.
Keywords :
distribution line , Oil-Immersed Transformer , Zinc Oxide Element , surge arrester , lightning
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399569
Link To Document :
بازگشت