Title of article :
An investigation of transient overvoltage generation when switching high voltage shunt reactors by SF6 circuit breaker
Author/Authors :
Ma، نويسنده , , Z.، نويسنده , , Bliss، نويسنده , , C.A.، نويسنده , , Penfold، نويسنده , , A.R.، نويسنده , , Harris، نويسنده , , A.F.W.، van der Steen, نويسنده , , Tennakoon، S. B. نويسنده , , S.B.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
8
From page :
472
To page :
479
Abstract :
The work reported in this paper can he grouped iinto three categories: empirical investigations, analytical studies and computer simulations. The studies have identified the causes of high transient overvoltages which are produced when switching high voltage shunt reactors. Laboratory and site testing hiave shown that multiple reignition is the most likely cause of the high overvoltages. Circuit analysis has been carried out to identify the conditions which lead to multiple reignitions. A computer model has been developed to allow the likelihood of multiple reignitions occurring to be assessed.
Keywords :
Shunt reactor switching , Circuit breaker , EMTP MODELS , Arc qodels. , Multiplereignitions
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399572
Link To Document :
بازگشت