Title of article :
Utilization of cable capacitance in GTO-HVDC transmission
Author/Authors :
Ziwen Yao، نويسنده , , Boon Teck Ooi، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
7
From page :
945
To page :
951
Abstract :
The voltage-source, GTO-HVdc stations require capacitor banks at their dc terminals for two purposes: (i) filtering of the GTO switching noise and {(ii) voltage support. This paper examines the feasibility of exploiting the capacitance of submarine andlor underground cables, thus offsetting some of the cost. It is shown that the capacitance of cable length as short as 10 km can significantly reduce the Total Harmonic Distortion (THD) of the dc voltage from 7.76% to 2.26%. However, the THD of the dc current is of the order of 18%. An inductor of 20mH (0.106 P.u.) is sufficient to reduce the current THD to 7%. The cable is modeled as L-R-C n section representation of the transmission line (1-section per km). The results are obtained by digital simulations (Matlab/Simulink).
Keywords :
cable transmission line , submarine , voltage-source converters , HVDC , GTO
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399635
Link To Document :
بازگشت