Abstract
Relevant standards establish the construction of a mean
curve in lightning impulies with perturbations (oscillations, overshoot,
noise) in order to determine the impulse characteristic parameters
(peak value, front time, time to half-value and voltage at
the instant of chopping and time to chopping if it is the case). In
the case of an impulse vrith overshoot the guidance given by the
IEC 60-1 standard in order to determine the existence of overshoot,
the duration of overshoot and the mean curve to be drawn
are not sufficient if digital recording systems are used. This problem
is studied and a procedure that uses the Kalman filtering
method in conjunction with acceptable criteria is described. Results
obtained with analytical impulses, real impulses and the reference
waveforms of the IEC 1083-2 standard are presented. Suggestions
to improve the actual standards are given.