Title of article :
The testing of SF6 generator circuit-breakers
Author/Authors :
Smeets، نويسنده , , R.P.P.، نويسنده , , Van der Linden، نويسنده , , W.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Pages :
6
From page :
1188
To page :
1193
Abstract :
Generator circuit-breakers face much higher current and voltage stress than distribution switchgear. This has led to a special standard (ANSI C37.013). Strictly in accordance with this standard’s requirements, test circuits and - parameters for a 100 kA and 120 kA (25.3 kV) SF, generator circuit-breaker have been defined. The circuit-breaker is equipped with capacitors at both sides of the extinction chambers. The effect of these is to reduce the TRV severity and this is quantified for the relevant switching duties. Adequate testcircuits are described. Also, the optional verification of interruption of generator-fed faults with very large dc components has been demonstrated. Herein, delayed current zero can extend arcing time. The importance of arc voltage in reducing the longer arcing time is illustrated in a calculated example.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1998
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399668