Title of article :
The testing of SF6 generator circuit-breakers
Author/Authors :
Smeets، نويسنده , , R.P.P.، نويسنده , , Van der Linden، نويسنده , , W.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Abstract :
Generator circuit-breakers face much higher
current and voltage stress than distribution switchgear. This
has led to a special standard (ANSI C37.013). Strictly in accordance
with this standard’s requirements, test circuits and -
parameters for a 100 kA and 120 kA (25.3 kV) SF, generator
circuit-breaker have been defined. The circuit-breaker is
equipped with capacitors at both sides of the extinction chambers.
The effect of these is to reduce the TRV severity and this
is quantified for the relevant switching duties. Adequate testcircuits
are described. Also, the optional verification of interruption
of generator-fed faults with very large dc components
has been demonstrated. Herein, delayed current zero can
extend arcing time. The importance of arc voltage in reducing
the longer arcing time is illustrated in a calculated example.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY