Abstract :
The paper is born as a contribution to the IEC 36A
Working Group 2 “Seismic qualification of bushings” in
order to evaluate the coefficients K (amplification factor
between the ground and the transformer bushing flange) and
R (response factor of the bushing itself) as defined in the IEC
61463 [l]. These coefficients allow the definition of the
seismic severity at the flange level to be used for static
calculations and vibrational tests on high voltage bushings.
For the evaluation of these coefficients both experimental onsite
dynamic tests and numerical finite element analyses have
been performed for a 160MVA, 2301135kV power
transformer [2]. The natural frequencies and the seismic
response of the whole transformer (tank, oil conservator and
HV bushings), subjected to different earthquakes, have been
calculated. At last a comparison between the calculated
coefficients (K and R) and those established by the IEC
61463 is illustrated.