A new method for detecting loss of synchronism using power and current measured on a line
Author/Authors
Minakawa، نويسنده , , T.، نويسنده , , Sato، نويسنده , , M.، نويسنده , , Ichikawa، نويسنده , , Y.، نويسنده , , Ishihara، نويسنده , , Y.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1999
Pages
6
From page
68
To page
73
Abstract
When a fault occurs, coherently swinging generators form
one group and the remaining ones form another . If the fault is severe,
loss of synchronism may take place between groups after single or
multiple swings. This paper proposes a new method for detecting loss
of synchronism. With this method, power and current are measured at
regular intervals on a tie-line linking sub-networks to which groups
of generators belong. Changes in power and current are calculated
during the interval, the location and direction of operating point of
power system moving on the curve of power versus phase angle is
estimated and the loss of synchronism is detected. The validity of
the method is shown by simulations using model networks.
Keywords
detection , Real time , Local Measurements , Loss of Synchronism , Power versus phase angle curve
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1999
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY