Title of article :
Modelling of HVDC wall bushing flashover due to uneven wetting
Author/Authors :
Tang، نويسنده , , L.، نويسنده , , Raghuveer، نويسنده , , M.R.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
6
From page :
194
To page :
199
Abstract :
An electric field based flashover model is proposed to predict the flashover voltage of an unevenly wetted HVDC wall bushing. Criteria for initiation and propagation of discharges have been incorporated in the model. The critical flashover voltage of a 600 kV wall bushing has been predicted and it is shown that the flashover stresses are very close to experimentally derived values, i.e. 60 - 70 kV/cm. Important aspects of wall bushing flashover such as critical dry zone length, the U-shaped characteristic of critical flashover voltage versus dry zone length, the effect of waterdrops, influence of ram conductivity and altitude are well reproduced and explained by the model.
Keywords :
HVDC wall bushings , Rain , uneven wetting , flashover mechanism , numerical model
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399748
Link To Document :
بازگشت