Title of article :
Cable crossings-derating considerations. II. Example of derivation of derating curves
Author/Authors :
Anders، نويسنده , , G.، نويسنده , , Brakelmann، نويسنده , , H.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
6
From page :
715
To page :
720
Abstract :
Cables crossing other heat sources either perpendicularly or at oblique angles will experience a rise in conductor temperature which should result in ampacity derating. In the first part of the paper a mathematical model for calculation of derating factors was presented. In this paper, a practical numerical example is considered with a pipe-type cable crossing a 10 kV distribution circuit. The numerical analysis presented here confirms experimental findings reported in the literature that the cable crossing may elevate conductor temperature by as much as 2OOC.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399818
Link To Document :
بازگشت