Title of article
Cable crossings-derating considerations. II. Example of derivation of derating curves
Author/Authors
Anders، نويسنده , , G.، نويسنده , , Brakelmann، نويسنده , , H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1999
Pages
6
From page
715
To page
720
Abstract
Cables crossing other heat sources either
perpendicularly or at oblique angles will experience a rise in
conductor temperature which should result in ampacity
derating. In the first part of the paper a mathematical model
for calculation of derating factors was presented. In this
paper, a practical numerical example is considered with a
pipe-type cable crossing a 10 kV distribution circuit. The
numerical analysis presented here confirms experimental
findings reported in the literature that the cable crossing may
elevate conductor temperature by as much as 2OOC.