Title of article :
Experimental validation of a thermal model for the ampacity derating of electric cables in wrapped trays
Author/Authors :
de Cassia A. Figueiredo، نويسنده , , R.، نويسنده , , Carneiro، نويسنده , , S.، نويسنده , , Cruz، نويسنده , , M.E.C.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Abstract :
As a safety measure for certain applications in Nuclear
Power Stations, cable trays must be wrapped with a fireproof
material. In this paper a new implementation of a thermal model is
presented, suitable for the determination of the ampacity derating
of electric cables in wrapped trays. Model simulation predictions
have been compared with field tests to validate the model. Bettgr
agreement between simulations and experimental results is
obtained when the standard procedure to determine the power loss
in the cable mass is modified to account for the actual measured
height of the cable mass in the tray.
Keywords :
Insulated Conductors , ampacity , Fire protection , Thermal Influences.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY