Title of article :
Experimental validation of a thermal model for the ampacity derating of electric cables in wrapped trays
Author/Authors :
de Cassia A. Figueiredo، نويسنده , , R.، نويسنده , , Carneiro، نويسنده , , S.، نويسنده , , Cruz، نويسنده , , M.E.C.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Pages :
8
From page :
735
To page :
742
Abstract :
As a safety measure for certain applications in Nuclear Power Stations, cable trays must be wrapped with a fireproof material. In this paper a new implementation of a thermal model is presented, suitable for the determination of the ampacity derating of electric cables in wrapped trays. Model simulation predictions have been compared with field tests to validate the model. Bettgr agreement between simulations and experimental results is obtained when the standard procedure to determine the power loss in the cable mass is modified to account for the actual measured height of the cable mass in the tray.
Keywords :
Insulated Conductors , ampacity , Fire protection , Thermal Influences.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1999
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399821