Title of article :
Design and field testing of a source based protection relay for wind farms
Author/Authors :
Haslam، نويسنده , , S.J.، نويسنده , , Crossley، نويسنده , , P.A.، نويسنده , , Jenkins، نويسنده , , N.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1999
Abstract :
The paper describes the design and field testing of a soufce
based relay suitable for the protection of wind farms with fixed-speed
induction generators. The relay provides short-circuit protection for
the medium voltage (MV) power collection circuit and the MV and
low voltage (LV) windings of each generator transformer. The use of
the relay allows a reduction in the construction cost of a wind farm,
since MV fuses are no longer required to protect the generator
transformers. The paper discusses how the protection algorithm was
designed based on the electrical behaviour of induction generators
operating in a wind farm. The relay was evaluated at a wind farm in
Wales and also in the laboratory using data from a wind farm
simulator and a transient recorder. The latter, installed at the wind
farm, recorded the voltage and current signals measured during local
disturbances. The recorded or simulated data was subsequently
replayed into a relay simulator which graphically describes the
operating behaviour of the protection.
Keywords :
Source Based Protection , Wind Farms , field testing , Multi-Function Relay
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY