• Title of article

    An investigation of zero order harmonics in power transformers

  • Author/Authors

    Warner، نويسنده , , D.E.، نويسنده , , Jewell، نويسنده , , W.T.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1999
  • Pages
    6
  • From page
    972
  • To page
    977
  • Abstract
    An investigation was done on the effects of zero order harmonics produced in a 7.5 h a single phase transformer using dc produced by injection on the primary from an external source and also by half wave rectification on the secondary with a resistive load. The accuracy of the disrrete fourier transform (dft) [l] for determining the dc component was also looked at, along with the ability of current transformers to detect a low frequencyl or quasi-de, component superimposed on an ac signal. Polynomial functions were developed to predict harmonic production, line current amplitude, input power, power factor, core losses, etc as functions of the dc current value for both cases. Results show a strong similarity in produced current harmonics for both cases. The dft is an accurate tool for determining the value of a dc component. Passive current transformers are not able to accurately detect a de, or slowly varying ac, component.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1999
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399854