Abstract
The effect of generator subtransient reactance, rotor
saliency, the number of generators in the Group Connection configuration
and adjustable speed operation on the commutation reactance
and harmonic levels of direct connected units are examined Restriction
limits for firing angles imposed by the commutation angle, generator
terminal power factor, equivalent continuous negativesequence
harmonic loading are derived that permit the use of n o d generators
in direct c o ~ e ~ t uendits without the need for extra harmonic loading
capacity. The generator harmonic ratings can be taken at the nominal
speed and rated power output.