• Title of article

    Factors affecting the commutation reactance of direct connected generator-converter units

  • Author/Authors

    Dinh، نويسنده , , Q.N.، نويسنده , , Arrillaga، نويسنده , , J.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1999
  • Pages
    6
  • From page
    1090
  • To page
    1095
  • Abstract
    The effect of generator subtransient reactance, rotor saliency, the number of generators in the Group Connection configuration and adjustable speed operation on the commutation reactance and harmonic levels of direct connected units are examined Restriction limits for firing angles imposed by the commutation angle, generator terminal power factor, equivalent continuous negativesequence harmonic loading are derived that permit the use of n o d generators in direct c o ~ e ~ t uendits without the need for extra harmonic loading capacity. The generator harmonic ratings can be taken at the nominal speed and rated power output.
  • Keywords
    Unit Connection , Group Connection , HVDC , Converter , Harmonics.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1999
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number