Abstract
The paper presents an apparent impedance calculation
procedure for distance relaying of transmission line involving
FACTS devices, particularly the UPFC (unified power flow controller).
The presence of UPFC significantly affects the trip boundaries
which are also adversely affected by fault resistance combined
with remote end infeed. Depending on the UPFC location,
the trip boundary is influenced by the fault location, prefault condition,
the arc fault resistance and the parameters of the UPFC
itself (series voltage magnitude and phase angle). The adaptive nature
of this protection scheme necessitates the use of a neural network
for generation of trip boundaries.
Keywords
Adaptive protection , protection setting. , FACTS , distance relaying