• Title of article

    Measurement of eddy-current loss coefficient PEC-R, derating of single-phase transformers, and comparison with K-factor approach

  • Author/Authors

    Fuchs، نويسنده , , E.F.، نويسنده , , Yildirim، نويسنده , , D.، نويسنده , , Grady، نويسنده , , W.M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2000
  • Pages
    7
  • From page
    148
  • To page
    154
  • Abstract
    A power amplifier is used to supply sinusoidal currents of different frequencies for measuring eddy-current losses of a 25 kVA single-phase transformer under short-circuit condition. Measured data show that eddy-current loss is a linear function of frequency with power of 2 and the eddy-current loss coefficient EC- linear is computed. New measurement techniques are applied to determine the derating of single-phase transformers with full-wave diode and thyristor rectifier loads. The derating of transformers has been defined such that for the (apparent, real) power transfer of a transformer the total losses are identical to the rated losses at rated temperature. A relation between apparent power, derating and K-factor is given taking into account iron-core and stray-power losses. Measured derating values are compared with computed results based on the eddy-current losses, iron-core losses, stray-power losses, and K-factors. The eddy-current loss coefficient EC- nonlinear is computed from harmonics caused by diode/thyristor bridge loads.
  • Keywords
    Eddy-current loss , K-factor , nonlinear load , transformer derating.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2000
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399955