Title of article :
Switching overvoltage analysis and air clearance design on the KEPCO 765 kV double circuit transmission system
Author/Authors :
Jeong Boo Kim، نويسنده , , Eung-Bo Shim، نويسنده , , Jeong-Woon Shim، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
This paper presents the results of the air clearance design
on the KEPCO 765 kV double circuit transmission system. At
first we performed the switching overvoltage study. The switching
overvoltage was analyzed by EMTP (Electro-Magnetic Transient
Program) and TNA (Transient Network Analyzer). The full scale
test for the air insulation strength of 765 kV double circuit transmission
tower was performed by 4MV outdoor impulse generator.
The simultaneous fault clearing case of single line-to-ground fault
at each circuit was considered because the probability of simultaneous
single line-to-ground fault at each circuit is very high. However,
the reclosing overvoltages with preinsertion resistor are lower
than the simultaneous fault clearing overvoltages when the transmission
line is short (about 170–180 km). The maximum phase to
ground switching overvoltage in the simultaneous fault clearing
case is 1.9 p.u. and the maximum switching overvoltage between
phase to phase is 3.3 p.u. The required air clearance in a tower at
the altitude of below 1000 m is 4950 mm to endure the maximum
switching overvoltage of 1.9 p.u. The standard deviation of 5% in
switching surge flashover voltage was verified from the full scale
test.
Keywords :
Air clearance , fault clearing , standard deviation , Flashover voltage , switching overvoltage.