Title of article :
Transmission line fault location for double phase-to-earth fault on non-direct-ground neutral system
Author/Authors :
Yao Zhang، نويسنده , , Qingchao Zhang، نويسنده , , Wennan Song، نويسنده , , Yixin Yu، نويسنده , , Xiao Li، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
5
From page :
520
To page :
524
Abstract :
An accurate algorithm for locating double phase-toearth fault on transmission line of nondirect ground neutral system is presented. The algorithm employs the faulted phase network and zero-sequence network as the fault location model. It effectively eliminates the effect of load flow and fault resistance on the accuracy of fault location. The technique embodies an accurate location by measuring only one local end data. The algorithm is used in a procedure that provides the automatic determination of faulted line and phase, rather than requires engineer to specify them. Simulation results have shown the effectiveness of the algorithm under the condition of earth faults.
Keywords :
transmission line. , nondirectground neutral system , Double phase-to-earth fault , Fault location
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2000
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
400010
Link To Document :
بازگشت