Title of article :
Efficient reduction of fault current through the grounding grid of substation supplied by cable line
Author/Authors :
Popovic، نويسنده , , L.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
The paper presents an analytical procedure suitable
for the determination of the part of the ground fault current emanating
from the substation grounding grid in the conditions when
a particular measure has been taken to reduce it. The practical realization
of this measure can be simply described as burying one
bare copper wire of a certain length in the same trench as the cable
feeding line. In the case of an overhead feeding line the similar measure
is denoted in the expert literature as the “counterpoise”. The
presented method enables a quick, and, for practical purposes, sufficiently
accurate evaluation of the copper wire length providing
the maximum possible reduction of the substation grid current.
The conveniences of the method result from the simplicity of the
formulae for the determination of the realized grid current reduction
at the effective copper wire length.
Keywords :
safety conditions. , Ground fault current distribution
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY